Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
16 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
Table 16: Link Test (Message Type 1) Byte Description
# Title Description
1 Header Character (h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
1
3-4 Receiver Number
Receiver gateway number from 01 to 99.
5 Line Number
Line number as zero for link test.
6-15 Spaces
Eleven spaces.
16-17 Event Code
Event code is @ for link test.
18-21 Spaces
Four spaces.
22 Trailer Character
Typically, this is HEX 14.
3.1.15 Robofon (Message Type j)
D6500 Byte Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Robofon
Example
h j r r l s s s s a a a a a a E E s s s s t
Table 17: Robofon (Message Type j) Byte Description
# Title Description
1 Header Character (h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
j
3-4 Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group Number
Line number in the receiver gateway that sent the message.
6-9 Spaces
Four spaces.
10-15 Account Number
Six digit account number.
16-17 EE
Event code.
18-21 Spaces
Four spaces.
22 Trailer Character
Typically, this is HEX 14.