Bosch Appliances D6600 Network Router User Manual


 
Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 47
3.2.25 Silent Knight FSK80 (Message Type E)
SIA Mode Description Silent Knight
FSK80 Example
<LF><CRC><E><sequence#><receiver#><line#>[#AAAA|NBAXY]<CR>
Table 79: Silent Knight FSK80 (Message Type E) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
E
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has four digits.
NBA
Alarm event
Figure 22: Message sent to printer
MM/DDsHH:MMsLxxsSFKsACCTsAAAA
+++ACCTsAAAAsALARM_ZNs1
+++ACCTsAAAAsALARM_ZNs2
+++ACCTsAAAAsALARM_ZNs3
+++ACCTsAAAAsALARM_ZNs4
+++ACCTsAAAAsALARM_ZNs5
+++ACCTsAAAAsALARM_ZNs7
+++ACCTsAAAAsALARM_ZNs8
+++ACCTsAAAAsALARM_ZNs9
Table 80: Silent Knight FSK80 Printer/LCD
output
Characters Description
MM/DDsHH:MM Date and time.
SFK SFSK80 format.
Lxx Line number.
AAAA The communicator's account number
has four digits.
s Space.