3.1.23 Silent Knight FSK2 (Message Type m)
D6500 Byte Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Silent Knight
FSK2 Example
h m r r l s a a a a a a a a “ E E Z Z “
*
*
*
t
Table 28: Silent Knight FSK2 (Message Type m) Byte Description
# Title Description
1 Header Character
(h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
m
3-4 Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group
Number
Line number in the receiver gateway that sent the message.
6 Spaces
One space.
7-14 Account Number
Maximum eight-digit account code. If the account code is less than eight digits, enter the
actual number of digits without a leading space.
15
Separator.
16-19 EEZZ
First event and zone number. If this is the only event, it will be ended with the terminator.
Up to eight reports. One report has four digits: one-digit event code, one-digit condition
code, two-digit zone code.
20
Separator.
21 ***
Next data.
22 Trailer Character
Typically, HEX 14.
3.1.24 Silent Knight FSK80 D6500 mode (Message Type E)
D6500 Byte Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Silent Knight
FSK80 Example
h E r r l s s s s s s A A A A s A s s X Y t
Table 29: Silent Knight FSK80 (Message Type E) Byte Description
# Title Description
1 Header Character
(h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
E
3-4 Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group
Number
Line number in the receiver gateway that sent the message.
6-11 Spaces
12-15 Account Number
Four-digit account number.
16 Space
17 Filler character A
Always char “A”.
18-19 Spaces
20-21 XY
Two-digit alarm zone code.
24 Trailer Character
Typically, HEX 14.