Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 37
3.2.12 FBI Super Fast (Message Type F)
SIA Mode Description FBI Super Fast
Example
<LF><CRC><F><sequence#><receiver#><line#>[#aaaa|TZZE]<CR>
Table 57: FBI Super Fast (Message Type F) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
F
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits are 01 to 99 for the D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits are 00
to 99. The receiver uses Line 0 (zero) for internal messages.
account#
The communicator's account number has four digits.
T
Zone type.
ZZ
Zone number.
E
Event type.
Figure 16: Message sent to printer
mm/ddshh:mmsLxxsFBIsACCTsaaaasTZZE+++s
ACCsaaaastttttttttseeeeeeeesiisnnn
For lines that are grouped, Gxx appears
instead of Lxx.
Table 58: FBI Super Fast (Message Type F)
Printer Output
Characters Description
FBI FBI Super Fast format.
Lxx: Line number.
Gxx Grouped line numbers.
Table 59: Event Code Table
Code Zone/Event Type
1 Fire
2 Panic
3 Burglary
4 Medical
5 Auxiliary
6 Bypass
7 Inactive
8 Eight
9 Nine
0 Zero
B Opening
C Closing
D Abort
E Restore
F Trouble
Table 60: Printer Output Codes
Characters Description
ii ZN=Zone number - ID=User ID
nnn Zone/User number.
ttttttttt Up to nine-character zone type, right
justified FIRE, PANIC, BURGLARY,
MEDICAL, AUXILIARY.
eeeeeeee Up to eight-character event type, left
justified ALARM, RESTORE, TROUBLE,
OPEN, OPENGRP, CLOSE, CLOSEGRP,
BYPASS, UN BYPASS, CANCEL.