Cisco Systems MDS 9100 Series Switch User Manual


 
A-3
Cisco MDS 9100 Series Hardware Installation Guide
OL-16187-01
Appendix A Cabinet and Rack Installation
Cisco MDS 9000 Family Telco and EIA Shelf Bracket
Requirements Specific to Solid-Walled Cabinets
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on
page A-1, solid-walled cabinets must meet the following requirements:
A roof-mounted fan tray and an air cooling scheme in which the fan tray pulls air in at the bottom
of the cabinet and exhausts it out the top, with a minimum of 500 cfm of airflow exiting the cabinet
roof through the fan tray.
Nonperforated (solid and sealed) front and back doors and side panels so that air travels predictably
from bottom to top.
The overall cabinet depth should be 36 to 42 in. (91.4 to 106.7 cm) to allow the doors to close and
adequate airflow.
A minimum of 150 sq. in. (968 sq. cm) of open area at the floor air intake of the cabinet.
The lowest piece of equipment should be installed a minimum of 1.75 in. (4.4 cm) above the floor
openings to prevent blocking the floor intake.
Requirements Specific to Standard Open Racks
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on
page A-1, if mounting the chassis in an open rack (no side panels or doors), ensure that the rack meets
the following requirements:
Width between two front mounting rails: minimum of 17.75 in. (45.1 cm)
Minimum vertical rack space per chassis: 1 rack unit (RU), equal to
1.75 in. (4.4 cm)
The distance between the outside face of the front mounting rail and the outside face of the back
mounting rail should be 23.5 to 34.0 in. (59.7 to 86.4 cm) to allow for rear bracket installation.
The distance between the chassis air vents and any walls should be 2.5 in. (6.4 cm).
Requirements Specific to Telco Racks
In addition to the requirements listed in the “General Requirements for Cabinets and Racks” section on
page A-1, telco racks should meet the following requirements:
The width of the rack between the two rack-mounting rails should be at least 17.75 in. (45.1 cm).
The distance between the chassis air vents and any walls should be 2.5 in. (6.4 cm).
Cisco MDS 9000 Family Telco and EIA Shelf Bracket
The optional telco and EIA Shelf Bracket Kit (part number DS-SHELF=) can temporarily or
permanently support the Cisco MDS 9100 Series during installation. Once the front rack-mount brackets
are securely attached to the rack-mounting rails, the shelf bracket can be removed.
This kit supports the following configurations:
A Cisco MDS 9100 Series switch in a two-post telco rack
A Cisco MDS 9100 Series switch in a four-post EIA rack