Emerson 200I/48-NT5C05C Switch User Manual


 
40 Functional description
UM5C05C P0745680 Standard 6.00 October 2001 Emerson Energy Systems
4.2.9. HVSD ( high voltage shutdown )
HVSD ADJ ( high voltage shutdown adjust ) potentiometer
Use this potentiometer to set the internal threshold level at which the local
high voltage shutdown condition should occur.
Remote HVSD
In addition to the local high voltage shutdown feature, the controller of the
power plant controller can shut down any rectifier by sending a high
voltage shutdown signal, ground ( BAT RTN ) pulse. The rectifier will
shut down within 50 ms if it is supplying more than 10% of its full load
rating.
As is the case for the internal high voltage shutdown condition, two HVSD
events must occur within an interval of two minutes to lock out the
rectifier permanently. An ac breaker reset or an HVSDR signal can be
used to restart the rectifier.
Local and remote HVSD reset
The rectifier may be reset from an HVSD condition locally by :
toggling the ac circuit breaker to OFF then to ON ( or the ac
breaker in the distribution panel )
sending a remote ground signal to the HVSDR input through the
controller restart ( provided the 'TR' lead has not been activated )
4.2.10. TR ( temporary inhibition ) and sequential start
Sequential start
The TR input can be interfaced to an external sequential start circuit.