4.2.3. Front panel LEDs
Table 10 - Designation of the LEDs on the front panel
LED Color Description
AC ON Green Input ac voltage operational
CL Yellow Current Limit
EQL Yellow Rectifier is in equalize mode
FAN ALM Red Fan fail alarm
HVSD Red High voltage shutdown
RFA Red Rectifier fail alarm
SEN FAIL Red Remote sense fail
THSD Red Thermal shutdown
AC ON ( ac voltage monitoring )
The rectifier monitors the input voltage and if the voltage exceeds the set
limit, it will inhibit its operation and trigger a rectifier failure alarm
( RFA ). The rectifier will resume its normal operation automatically when
the specified input voltage has been re-established.
CL ( current limit indicator )
This LED lights up if the rectifier is in current limit. The rectifier limits
the output current to 205 A +
5 A ( adjusted in the factory ), 50% to 105%
of the rated output current.
EQL ( equalize )
Indicates the rectifier is in equalizing mode.
FAN ALM ( fan failure alarm )
This LED lights up when the FAN ALM is activated due to a defect in the
fan system. The fan configuration includes redundancy to ensure the
rectifier will continue working properly if one of the fans fails. If only one
fan fails, a rectifier failure alarm RFA will not be triggered. It is, however,
imperative to repair or change the fan unit as soon as possible to preserve
this redundant feature.