7. Troubleshooting
Table 16 - Diagnosing system faults
Fault symptom Possible causes
The RFA LED is lit.
No ac input or input is out of bounds ( ac ON
LED is extinguished ).
AC Input / dc output circuit breaker is open.
The rectifier has received an HVSD signal from
the controller, or a TR signal is present.
An internal high voltage shutdown ( HVSD ) has
occurred.
Two cooling fans or fuses have failed.
The inrush fuse has blown.
The dc circuit breaker is open.
A thermal shutdown has occurred.
Ambient air temperature is high.
Air inlet / outlet air is blocked, or the air filter is
clogged.
A rectifier is in 'Start Time Delay' mode and the
RFA will cease when the required time delay has
elapsed.
Defective rectifier.
The HVSD LED is lit. The internal high voltage shutdown point is set
to low ( below the float or equalize setting ).
The controller triggered a remote HVSD.
continued