The MPS601 is housed in 1U tall, half rack width, six inches deep metal enclosure,
rack- or desk-mountable. The switcher can be mounted through-desk or rackmounted with
optional rack mount brackets. The switcherscan also be surface-mounted under a table,
desk, or podium, or on a wall, using an optional under-deskmounting kit
(see www.extron.com).
UL Rack Mounting Guidelines
The following Underwriters Laboratories (UL) guidelines pertain to the safe installation of the
MPS601 in a rack.
1. Elevated operating ambient temperature — If installed in a closed ormulti-unit
rack assembly, the operating ambient temperature of the rack environmentmay be
greater than room ambient temperature. Therefore, install the device in an environment
compatible with themaximum ambient temperature (Tma = +122 °F, +50 °C) specified
by Extron.
2. Reduced air flow — Install the equipment in a rack so that the amount of air flow
required for safe operation of the equipment is not compromised.
3. Mechanical loading — Mount the equipment in the rack so that a hazardous
condition is not achieved due to unevenmechanical loading.
4. Circuit overloading — Connect the equipment to the supply circuit and consider the
effect that circuit overloadingmight have on overcurrent protection and supply wiring.
Appropriate consideration of equipment nameplate ratings should be used when
addressing this concern.
5. Reliable earthing (grounding) — Maintain reliable grounding of rack-mounted
equipment. Pay particular attention to supply connections other than direct connections
to the branch circuit (e.g. use of power strips).