LG Electronics SV-iC5 Series Power Supply User Manual


 
10. Advanced functions
10-16 SV-iC5
Carrier frequency select
Group LED Display Parameter Name
Set
value
Min/Max
Range
Factory
Defaults
Unit
Function
group 2
H39 [Carrier frequency select] -
0/15 10
This parameter affects the sound of the inverter during operation.
Motor noise
v
Heat loss of the inverter
u
Inverter noise
u
H39 If carrier frequency set higher
Leakage current
u
10.13 Second motor operation
Group LED Display Parameter Name
Set
value
Min/Max
Range
Factory
Defaults
Unit
H81
[2
nd
motor Accel time]
- 0/6000 5.0 Sec
H82
[2
nd
motor Decel time]
- 10.0 Sec
H83
[2
nd
motor base frequency]
- 30/400 60.0 Hz
H84
[2
nd
motor V/F pattern]
- 0/2 0
H85
[2
nd
motor forward torque
boost]
- 0/15 5 %
H86
[2
nd
motor reverse torque
boost]
- 5 %
H87
[2
nd
motor stall prevention
level]
- 30/200 150 %
H88
[2
nd
motor Electronic thermal
level for 1 min]
- 50/200 150 %
H89
[2
nd
motor Electronic thermal
level for continuous]
- 100 %
Function
group 2
H90
[2
nd
motor rated current]
- 0.1/20 1.8 A
I20
[Multi-function input terminal
P1 define]
- 0
~
~
I/O group
I24
[Multi-function input
terminal P5 define]
12
0/24
4
Select the terminal among Multi-function input P1 thru P5 for second motor operation.
If using the terminal P5 for second motor operation, set I24 to 12.