LG Electronics SV-iC5 Series Power Supply User Manual


 
11. Monitoring
11-5 SV-iC5
11.4 Analog Output
Group LED Display Parameter Name
Set
value
Min/Max
range
Factory
default
Unit
I50
[Analog output item
select]
-
0/3
0
I/O group
I51
[Analog output level
adjustment]
-
10/200
100 %
Output item and the level from the AM terminal are selectable and adjustable.
I50 : The selected item will be output to Analog output terminal (AM).
10V
0 Output frequency. Max Frequency (F21)
1 Output current 150% of Inverter rated current
2 Output voltage 282 Vac
I50 Analog output
item select
3
Inverter DC link
voltage
400 Vdc
I51 : If you want to use Analog output value as a gauge input , the value can be adjustable