7. Function list
7-1 SV-iC5
7. Function list
Drive Group
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
0.0
[Frequency
command]
0/400
[Hz]
This parameter sets the frequency that the
inverter is commanded to output.
During Stop: Frequency Command
During Run: Output Frequency
During Multi-step operation: Multi-step
frequency 0.
It cannot be set greater than F21- [Max
frequency].
0.0 O 9-1
ACC [Accel time] 5.0 O 9-10
dEC [Decel time]
0/6000
[sec]
During Multi-Accel/Decel operation, this
parameter serves as Accel/Decel time 0.
10.0 O 9-10
0 Run/Stop via Run/Stop key on the keypad 9-7
1
FX : Motor forward run
RX : Motor reverse run
2
Run/Stop
via control
terminal
FX : Run/Stop enable
RX : Reverse rotation select
9-7
Drv [Drive mode]
(Run/Stop
mode)
0/3
3 Operation via Communication Option
1 X
0 Setting via Keypad 1 9-1
1
Digital
Setting via Keypad 2 9-1
2
Setting via potentiometer on
the keypad(V0)
9-2
3 Setting via V1 terminal 9-3
4 Setting via I terminal 9-3
5
Setting via potentiometer on
the keypad + I terminal
9-4
6 Setting via V1 + I terminal 9-4
7
Setting via potentiometer on
the keypad + V1 terminal
9-5
Frq [Frequency
mode]
0/8
8
Analog
Modbus-RTU Communication
0 X
St1 [Multi-Step
frequency 1]
This parameter sets Multi-Step frequency 1
during Multi-step operation.
10.0 O 9-6
St2 [Multi-Step
frequency 2]
This parameter sets Multi-Step frequency 2
during Multi-step operation.
20.0 O 9-6
St3 [Multi-Step
frequency 3]
0/400
[Hz]
This parameter sets Multi-Step frequency 3
during Multi-step operation.
30.0 O 9-6