LG Electronics SV-iC5 Series Power Supply User Manual


 
14. Specifications
14-2 SV-iC5
Multi-function relay
terminal
Fault output (N.O., N.C.)
Analog output 0 ~ 10 Vdc : Frequency, Current, Voltage, DC link voltage selectable
Protective functions
Inverter Trip
Over-voltage, Under-voltage, Over-current, Ground fault current detection, Over-temperature of inverter
and motor, Output phase open, Overload, Communication error, Loss of frequency command, H/W fault
Alarm
Conditions
Stall prevention, Overload
Momentary
power loss
Less than 15 msec : Continuous operation
More than 15 msec : Auto Restart enable
Environment
Cooling
method
Forced air cooling
Degree of
protection
Open, Pollution degree 2
Ambient
temperature
-10°C ~ +50°C
Storage
temperature
-20°C ~ +65°C
Relative
humidity
Less than 90% (no condensation)
Altitude,
Vibration
1,000m above sea level, Max. 5.9m/sec
2
(0.6G)
Application
site
Protected from corrosive gas, combustible gas, oil mist or dust