LG Electronics SV-iC5 Series Power Supply User Manual


 
9. Basic functions
9-7 SV-iC5
9.3 Run Command setting
Run via the Run and STOP/RST key
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
drv
[Drive mode]
(Run/Stop mode)
0
0/3 1
Drive
group
drC
[Direction of motor rotation
select]
- F/r F
Set drv – [Drive mode] to 0.
Motor starts to accelerate by pressing the Run key while run frequency is set. Motor decelerates to stop by
pressing the STOP/RST key.
Selecting rotation direction is available at drC - [Direction of motor rotation select] when run command is
issued via Run key on keypad.
FForward
drC [Direction of motor
rotation select]
R Reverse
Run command setting 1 via FX and RX terminals
Group LED Display Parameter Name
Set
Value
Min/Max
Range
Factory
Defaults
Unit
Drive
group
drv
[Drive mode]
(Run/Stop mode)
1
0/3 1
I20
[Multi-function input terminal
P1 define]
0 0/24 0
I/O group
I21
[Multi-function input terminal
P2 define]
1 0/24 1
Set drv – [Drive mode] to 1.
Set I20 and I21 to 0 and 1 to use P1 and P2 as FX and RX terminals.
“FX” is Forward run command and “RX” Reverse run.
Operation will stop when both FX and RX terminals are turned ON or OFF.
FX : Counter clockwise
FX
RX
Frequency