7. Function list
7-8 SV-iC5
Function group 2
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
H 0 [Jump code] 1/95 This parameter sets the code number to jump. 1 O 5-5
H 1 [Fault history 1] - nOn -
H 2 [Fault history 2] - nOn -
H 3 [Fault history 3] - nOn -
H 4 [Fault history 4] - nOn -
H 5 [Fault history 5] -
This parameter stores information on the
types of faults, the frequency, the current and
the Accel/Decel condition at the time of fault.
The last fault is automatically stored in the
H 1- [Fault history 1].
nOn -
H 6 [Reset fault
history]
0/1 This parameter clears the fault history
saved in H 1-5.
0 O
11-4
H 7 [Dwell
frequency]
F23/400
[Hz]
When run frequency is issued, motor starts
to accelerate after dwell frequency is applied
to the motor during H8- [Dwell time].
[Dwell frequency] can be set within the
range of F21- [Max frequency] and F23- [Start
frequency].
5.0 X
H 8 [Dwell time] 0/10 [sec] This parameter sets the time for dwell
operation.
0.0 X
10-5
H10 [Skip
frequency
select]
0/1 This parameter sets the frequency range to
skip to prevent undesirable resonance and
vibration on the structure of the machine.
0 X
H11
1)
[Skip
frequency low
limit 1]
10.0 X
H12 [Skip
frequency high
limit 1]
15.0 X
H13 [Skip
frequency low
limit 2]
20.0 X
H14 [Skip
frequency high
limit 2]
25.0 X
H15 [Skip
frequency low
limit 3]
0/400
[Hz]
Run frequency cannot be set within the
range of H11 thru H16.
The frequency values of the low numbered
parameters cannot be set above those of the
high numbered ones.
30.0 X
9-20