LG Electronics SV-iC5 Series Power Supply User Manual


 
7. Function list
7-3 SV-iC5
Function group 1
LED
display
Parameter
name
Min/Max
range
Description
Factory
defaults
Adjustable
during run
Page
F 0 [Jump code] 0/60 This parameter sets the parameter code
number to jump.
1 O 5-5
0 Fwd and rev run enable
1 Forward run disable
F 1
[Forward/
Reverse run
disable]
0/2
2 Reverse run disable
0 X 9-8
F 2 [Accel pattern] 0 Linear
F 3 [Decel pattern]
0/1
1 S-curve
0 X 9-13
0
Decelerate to stop
1 Stop via DC brake
F 4 [Stop mode
select]
0/2
2 Free run to stop
0 X 9-18
F 8
1)
[DC Brake
start
frequency]
0/60 [Hz] This parameter sets DC brake start
frequency.
It cannot be set below F23 - [Start
frequency].
5.0 X 10-1
F 9 [DC Brake
wait time]
0/60 [sec] When DC brake frequency is reached, the
inverter holds the output for the setting time
before starting DC brake.
0.1 X 10-1
F10 [DC Brake
voltage]
0/200
[%]
This parameter sets the amount of DC
voltage applied to a motor.
It is set in percent of H33 – [Motor rated
current].
50 X 10-1
F11 [DC Brake
time]
0/60 [sec] This parameter sets the time taken to
apply DC current to a motor while motor is at
a stop.
1.0 X 10-1
F12 [DC Brake
start voltage]
0/200
[%]
This parameter sets the amount of DC
voltage before a motor starts to run.
It is set in percent of H33 – [Motor rated
current].
50 X 10-2
F13 [DC Brake
start time]
0/60 [sec] DC voltage is applied to the motor for DC
Brake start time before motor accelerates.
0 X 10-2
F14 [Time for
magnetizing a
motor]
0/60 [sec] This parameter applies the current to a
motor for the set time before motor
accelerates during Sensorless vector control.
1.0 X 10-11
1) : Set F4 to 1 (Stop via DC brake ) to view this function