MGE UPS Systems S3 Power Supply User Manual


 
Table : Recommended Input/Output Wiring
2- 1
Model DC Input AC Output AC Input
Current Current Current
Max.
Current 63054 16 AMPS 5 AMPS 5 AMPS
Min. Wire
Size (500VA) 12 AWG 14 AWG 14 AWG
Max.
Current 63104 30 AMPS 10 AMPS 10 AMPS
Min. Wire
Size (1kVA) 10 AWG 14 AWG 14 AWG
Max.
Current 63204 60 AMPS 17 AMPS 17 AMPS
Min. Wire
Size (2kVA) 8 AWG 12 AWG 12 AWG
NOTE: Maximum circuit breaker rating for AC input shall be
20 Amperes, Maximum DC input current should be limited
to 50 Amperes. Wire gauge for both AC and DC wiring shall
be selected according to the national electrical code.
WARNING
This product is considered permanently connected equipment and
must have a readily accessible disconnect device incorporated in the
fixed wiring.
ATTENTION
Ce produit est considere comme equipement connecte en permanence
et doit avoir un appareil de deconnexion facilement accessible incor-
pore dans le cablage fixe.
WARNUNG!
Dieses Produkt ist ein fest zusammengefuegtes Geraet und muss eine
leicht erreichbare Abschaltungsvorrichtung im Leitungsnetz enthal-
ten.
2 — 4 Installation and Operation 86-153061-00
Topaz S3 Inverters 0.5 kVA, 1 kVA, & 2 kVA