MGE UPS Systems S3 Power Supply User Manual


 
These dimensions include both the receiver cabinet and the
inverter module. Depth is inclusive of the inverter module
thumb screws.
0.5 kVA, 1 kVA 2 kVA
HEIGHT: 3.50 in (8.9 cm) 5.3 in (13.4 cm)
WIDTH: 17.0 in (43.2 cm) 17.0 in (43.2 cm)
DEPTH: 19.0 in (48.3 cm) 19.0 in (48.3 cm)
0.5 kVA & 1 kVA 2 kVA
Receiver cabinet 8.0 lbs (3.63 Kg) 11 lbs (5 Kg.)
Inverter module 23.0 lbs (10.44 Kg) 31 lbs. (14 Kg.)
Total weight with
mounting brackets 39.0 lbs (17.7 Kg). 51 lbs. (23.18 Kg.)
Continuous overload to 125% of rated VA/Watts @ 50
degrees celsius maximum for 0.5 kVA & 1 kVA, and 120% of
rated VA/Watts @ 40 degrees celsius for 2 kVA. Full output
power/VA and short term (30 seconds) overload to 125%
between -10 to +50 degrees celsius. Derate power/VA
linearly to zero between +50 and +70 degrees celsius.
-40 to +75 degrees celsius. for shipping, but not
recommended for storage. See Section 2.3 for storage
recommendations.
0 to 90% relative, without condensation.
To 10,000 feet above sea level. Derate maximum ambient of
50 degrees celsius by 3 degrees celsius per 1000 ft. at
altitude above 3300 feet (30 degrees celsius maximum at
10,000 feet).
Less than 60 dBA per Type 2, IEC and ANSI SI.4, 1981 when
measured in a 55 dBA environment at a distance of 4 feet
from any surface.
Forced air. Air inlet is located on the front panel. Exhaust is
out the sides of the receiver cabinet. See Figure 2-1.
1.8.6 Cooling
1.8.5 Audible Noise
1.8.4 Operating Altitude
1.8.3 Operating Humidity
1.8.2 Non-Operating
Temperature
1.8.1 Operating
Temperature
1.8 Environmental
Specifications
1.7.2 Weight
1.7.1 Dimensions
86-153061-00 1 — 15Introduction
Owner’s Manual