Table : Characteristics of Inverter
1- 1
Model Output Nominal Input Max. Nominal Output AC Amperes at
Number Power Input Voltage Input DC Selectable Output Voltage of:
Rating Voltage Range Current
(VA/Watts) (Vdc)** (Vdc) Amperes 120V 220V 230V 240V
63204* 2000/1680 -48 42 to 57 60 16.6 8.4 8.4 8.4
63104* 1000/840 -48 40 to 60 30 8.3 4.2 4.2 4.2
63054* 500/420 -48 40 to 60 16 4.2 2.1 2.1 2.1
*Model number is followed by a two-digit dash number:
-92 = Inverter with Status indicators.
-94 = Inverter with Status indicators, Digital LCD, and Static Transfer Switch.
**DC voltage rating is given with respect to earth or chassis ground.
0.5 microsecond, 100 kHz ringing wave with 6000V peak,
with no resulting damage per IEEE587.
Less than 30 dBrnC.
80% minimum (on-line mode).
97% typical (off-line mode).
1.5.3 Efficiency