Mitsubishi Electronics SH-080007 Network Card User Manual


 
7 - 14 7 - 14
MELSEC-Q
7 DATA COMMUNICATIONS USING BIDIRECTIONAL PROTOCOL
(2) Confirmation using the module and GX Configurator-SC
1) Confirmation using the display LED
When the Q series C24 detects an error, including a transmission error, the
ERR LED lights up. (See Chapter 10.)
2) Confirmation using GX Configurator-SC
• The monitor function is used to check for errors. (See Sections 8.6.3 and
8.6.6.)
• The ERR LED is turned off with the ERR LED OFF function. (See Section
8.6.10.)
3) Confirming the error code
Use one of the following to confirm the error code.
• GX Configurator-SC monitor function (See Section 8.6.6.)
• GX Developer buffer memory monitor function (monitors addresses
258
H
/268
H
)
(3) Handling of receive data when a reception error occurs
1) All of the receive data for which an error was detected is ignored and an
response message indicating an abnormal completion (NAK message) is
sent to the external device.
When an error is detected during message reception, the Q series C24
does not issue a reception data read request to the PLC CPU.
2) The receive area in the buffer memory will contain the data received normally
just prior to the error occurrence. (Data will not be rewritten.)
7.1.5 Receive data clear
Data communications using the bidirectional protocol must be performed after a
response message is received in reply to the preceding data transmission.
If the Q series C24 detects an error while receiving data, it sends an NAK message
(response message) to the external device after the data reception completion and
ignores the data being received when the error was detected.
Therefore, the receive data does not have to be cleared.