10 - 41 10 - 41
MELSEC-Q
10 TROUBLESHOOTING
10.3.14 Troubleshooting when data cannot be communicated via modem
Symptom Cause Corrective action MC
Non
procedure
protocol
Bidirection
al protocol
• A modem initialization error occurs.
• Check the error code and execute
processing accordingly.
• Modem connection channel designation is
not performed.
• Set Modem connection channel
designation.
• Auto modem initialization
cannot be executed.
• There is an error in the switch settings in the
GX Developer.
• Review the switch settings. Set it to match
the local station modem and the TA.
• Communication protocol setting is incorrect.
• Set the communication protocol to MC
protocol, format 5.
• Transmission setting does not match the
external device.
• Review the transmission setting.
• Data cannot be
communicated with GX
Developer supporting the Q
series C24.
• Communication rate does not match the
external device.
• Review the communication rate setting.
• The product is not supported by the GX
Developer.
• Confirm the GX Developer’s S/W version.
• There was an error in the GX Developer
connection system.
• Check the GX Developer’s connection
system.
• Set the connection system on “callback
reception waiting” and connect.
• The GX Developer does not
receive the callback signals
from the Q Series C24.
• There is an error in the GX Developer side’s
modem settings.
• Set the modem’s settings on "Auto
Reception."
• There s an error in the GX Developer’s
connection system.
• Check the GX Developer’s connection
system.
• Correct the Q Series C24’s settings.
• Callback connections from
the GX Developer are
refused by the Q Series
C24.
• There is an error in the connection system’s
telephone No.
• Check the telephone No.
• Change the telephone No. to the data for
callback.
• There is an error in the Q Series C24
setting value.
• Set the callback function designation on the
setting 1 to 3.
• There is an error in the GX Developer’s
connection system.
• Check the GX Developer’s connection
system.
• Check the Q Series C24’s settings.
• When performing Auto
(callback: during fixed/
during designated number)
from the GX Developer,
connection to the Q Series
C24 is refused.
• There is an error in the telephone No. of the
connection system.
• Check the telephone No.
• Change the telephone No. to the data for
callback.
• The timer value for the status of the modem
used or the line is short.
• Adjust each of the timer values for the
callback function on the GX Developer side.
(Line callback cancel wait time, callback
delay time)
• It is possible to connect
from the GX Developer, but
callback from the Q Series
C24 cannot be performed.
• There is a problem with the modem
specifications or settings.
• Check the modem’s specifications and
settings.