Mitsubishi Electronics SH-080007 Network Card User Manual


 
10 - 18 10 - 18
MELSEC-Q
10 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Error Contents
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
7E52
H
User frame
overwrite error
A written frame No. overwrite request was issued. PRO
Change the write destination to
an unwritten frame No.
When overwriting, delete the
given No. beforehand.
7E53H
User frame access
data error
A nonexistent command was designated in a
subcommand.
Byte count exceeding the number of bytes that can
be requested was designated.
PRO
Check and correct the external
device transmit message and
restart data communications.
7E54H
Modification
allowed error
Flash ROM write allow/prohibit designation from GX
Configurator-SC is set to OFF.
At the switch setting on GX Developer, modification
allowed switch was set to OFF.
PRO
Set to ON at GX Configurator-
SC.
Set to ON at GX Developer.
7E55
H
User frame data
error
There is an error in the user frame variable data. PRO
Check and correct the external
device transmit message and
restart data communications.
7E56
H
System error The OS of the Q series C24 detected some error. ( 1)
7E57H
Flash ROM write
error
Cannot write to Flash ROM normally. PRO
Re-execute the write operation.
If the error is generated again,
replace the module.
7E58
H
Mode modification
error
There was an error in the mode No. or transmission
specification designated contents when changing
the mode.
PRO
Check and correct the contents
of the external device transmit
message and restart data
communications.
Recheck the switch setting on
the Q series C24.
7E59H
Flash ROM write
count over limit
error
Flash ROM written 1,000 times
Review the program.
Rewrite the flash ROM area
(address: 2401
H) of the buffer
memory to 0 and restart data
communications.
7E5F H
I/O number error
on requested
module
I/O number of requested module is incorrect.
Correct the I/O number of the
module to which data is sent.
7E60
H
Device monitoring
duplicate
registration error
PLC CPU monitoring registration was performed
twice.
Cancel the PLC CPU monitoring
and perform the PLC CPU
monitoring registration again.
7E61
H
Cycle time units
range error
Setting value of cycle time units is out of range.
Correct the setting value of the
cycle time units.
7E62 H
PLC CPU
monitoring function
error
Setting value of PLC CPU monitoring function is out
of range.
Correct the setting value of the
PLC CPU monitoring function.
7E63 H
Transmission
measure setting
error
Setting of transmission measure of the PLC CPU
monitoring is incorrect.
Correct the setting value of the
transmission measure.
7E64
H
Registration point
range error
Registration point (word/bit) is out of range.
Correct the setting value of the
registration point (word/byte)
7E65
H
PLC CPU abnormal
monitoring number
error
Setting value of the PLC CPU abnormal monitoring
is out of range.
Correct the setting value of the
PLC CPU abnormal monitoring.
7E66
H
Monitoring
condition error of
monitoring device
Setting value of transmission condition is out of
range.
Correct the setting value of the
transmission condition.
7E67 H
CPU abnormal
monitoring setting
value error
Setting value (fixed value) of CPU abnormal
monitoring is out of range.
Correct the setting value (fixed
value) of the CPU abnormal
monitoring.
7E68
H
Transmission
condition range
error of monitoring
device
Setting value of transmission condition (condition
agreement transmission) is out of range.
Correct the setting value of the
transmission condition
(condition agreement
transmission).
7E69H
CPU abnormal
monitoring setting
value error
Setting value (fixed value) of CPU abnormal
monitoring is out of range.
Correct the setting value (fixed
value) of the CPU abnormal
monitoring.