Omron CJ2H-CPU6@-EIP Network Card User Manual


 
396
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E
Total Number of Packets Sent (Response)
The total number of packets sent by the EtherNet/IP Unit or built-in EtherNet/IP port is returned.
Total Number of Errors Sent (Response)
The total number of packet errors detected while the EtherNet/IP Unit or built-in EtherNet/IP port was sending
is returned.
Total Number of Send Collisions (Response)
Returns the number of packets damaged by 16 collisions with data from other nodes during EtherNet/IP Unit or
built-in EtherNet/IP port transmissions.
Precautions
Counting of the total number of packets received, total number of receive errors, total number of packets sent,
total number of errors sent, and total number of send collisions is discontinued when the counted value
reaches the maximum value.
Response Codes
INTERNODE ECHO TEST
Performs an echoback test (internode communications test) between specified nodes.
Command Block
Response Block
Parameters
Test Data (Command, Response)
This command specifies the data to be sent to the specified nodes. Up to 1,998 bytes can be specified. The
response sends back data identical to the data specified in the command. An abnormality is assumed if the
data returned in the response differs from the test data sent.
Precautions
The test destination node is the destination node specified in the CMND(194) instruction operands.
Always specify the unit address of the EtherNet/IP Unit or built-in EtherNet/IP port in the CMND(194)
instruction.
Response code Description
0000 Normal end
1001 Command too large
08 01
Command
code
1,998 bytes max.
Test data
08 01
Response
code
Command
code
1,998 bytes max.
Test data