Omron CJ2H-CPU6@-EIP Network Card User Manual


 
406
FINS Commands Addressed to EtherNet/IP Units or Built-in EtherNet/IP Ports Appendix E
FINS Node Address
Node address for communications via the FINS command (in hexadecimal).
IP Address
IP number used by TCP/IP protocol (in hexadecimal).
Precautions
If the IP address table contains fewer records than the number specified in the number of records parame-
ter, all the records contained in the IP address table when the command is executed will be returned and
the command execution will end normally.
An error response will be returned if the IP address conversion method in the system mode settings is set
to the automatic generation method on the FINS/UDP Tab Page of the Unit.
Response Codes
IP ROUTER TABLE READ
Reads the IP router table.
Command Block
Response Block
Parameters
Number of Records (Command, Response)
The number of records to read is specified between 0000 and 0008 (0 to 8 decimal) in the command. If this
value is set to 0, the number of stored records will be returned but the IP router table records will not be
returned. The response returns the actual number of records read.
FINS node
number
1
00
IP address
6 byte
s
Response code Description
0000 Normal end
1001 Command too large
1002 Command too small
2307 IP address conversion method is set to the automatic genera-
tion method.
Number
of records
Command
code
27 61
Maximum
number
of stored
records
Number
of stored
records
Number
of records
IP router
table records
Response
code
Command
code
27 61
IP router
table records
8 bytes 8 bytes