CS4000 Mini Controller with Ethernet
Page
3-12
T-38324-A 39-30-38324
Backplane Fuses
Fuse F4 is Littelfuse 239001, 5x20 mm, 1A, SLO BLO (SB) 250V (part number 13-10-61001). Fuse
F4 protects the DCM board inside the TCM.
Fuses F2 and F3 are Littelfuse 255.500, subminiature 0.5A (part number 13-10-4050). Fuse F2
protects the 24VDC to the tool, and Fuse F3 protects the 24VDC used with the discrete I/O circuits.
Address Switches
Each TCM has a unique serial address. The first six DIP switches on the address switch, SW-1, allow
you to set up the communication address, 1 to 32, for the TCM.
Switch 7 assigns the baud rate at which the TCM sends data to an attached computer. When switch 7
is in the OFF position, a baud rate of 9600 kbps is used. When switch 7 is in the ON position, a baud
rate of 57600 kbps is used. Switch 8 is used to set up the TCM for the “PFCS” Mode used by the
DaimlerChrysler Plant Floor Communication System.