SPX Cooling Technologies CS4000 Switch User Manual


 
CS4000 Mini Controller with Ethernet
Page
5-10
T-38324-A 39-30-38324
Updating Application Settings
After you have flashed an application file to the Ethernet interface card, you may want to update
settings without re-flashing the entire application file again. To do this, the TINI Ethernet Flash Utility
has a menu option that allows you to update the IP address, subnet mask and default gateway values,
and enable or disable application functions for the Ethernet network and RS-422 link.
Use Procedure 5-2 to edit application settings.
Procedure 5-2. Editing Application Information
1. If necessary, repeat Steps 1 to 9 from Procedure 5-1 on page 5-2 to connect the
laptop to the Ethernet interface card inside the controller.
2. Select TINI Application Info….
a. Click the Flash menu in the TINI Ethernet Flash Utility window.
b. From the Flash menu, select S
et TINI Application Info….
Figure 5-12. Selecting the “Set TINI Application Info…”
Menu Option