Toshiba G8000 Series Power Supply User Manual


 
9
Inspection/Storage/Disposal
Inspection
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing
the unit from the pallet. Refer to labels or documentation attached to packing material.
Uncrating
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping,
keep all original crating and packing materials for return to the shipping agent. The warranty does not apply to
damage incurred during shipping.
Ensure that the rated capacity and the model number specified on the nameplate conform to the order
specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
1) Power up the UPS and allow it to operate with no load for 24 hours to fully charge the batteries.
2) Stop the unit.
3) Place the MCCB switch in the "Off" position.
Storing Conditions
For best results, store the UPS in the original shipping container and place on a wood or metal pallet.
Storage temperature — -20 – 40° C (-4 – 104° F).
The optimum storage temperature is 21° C (70° F). A higher ambient temperature will require recharging
more frequently during storage.
Avoid the following storage locations:
Locations that are subject to extreme temperature changes or high humidity.
Locations that are subject to high levels of dust or metal particles.
Locations that are subject to excessive vibration.
Inclined floor surfaces.
CAUTION