Toshiba G8000 Series Power Supply User Manual


 
46
* To change from Bypass to UPS supply, follow the procedure step #5 in Table 13. If the AC
switch does not function, contact Toshiba or authorized representatives.
14.3.3 Stop
Table 15 shows the procedure to stop the UPS.
Table 15 - Stopping procedure.
Step Procedure LCD/LED Status
1
Transfer to Bypass
supply as described in
Table 14.
UPS LED is off and BYPASS LED is on.
2
Turn off the DC input
breaker, and, press the
“STOP” button for 0.5
sec at least.
BATTERIES LED is off and INVERTER LED flashes then
off.
FLOAT CHARGE LED and CONVERTER LED are off.
BYPASS
AC-VO 480[V]
AC- I O 50[%]
PRESS ‘UPS’ SWITCH
AC
SWITCH
UPS
BYPASS
BATTERIES
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
AC INPUT
~
CONVERTER
~
INVERTER
AC OUTPUT
BYPASS INPUT
BYPASS
MOVE #72B TO ‘OFF’ POSITION
AC
SWITCH
UPS
BYPASS
BATTERIES
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
AC INPUT
~
CONVERTER
~
INVERTER
AC OUTPUT
BYPASS INPUT