47
3
Please wait.
→Procedure
completed.
14.3.4 Complete Shutdown
This section shows the procedure to turn off the control power and shut down the UPS
completely.
Table 16 - Complete Shutdown.
Step Procedure LCD/LED Status
1-3 Same as steps 1-3 in "Stop" section.
4 Scroll the LCD screen
to see the DC INPUT
and make sure DC bus
voltage is 0V.
5 *Turn off the control
power supply switch
(8A).
Nothing is displayed on the LCD and all LED’s are off.
6 Turn off all breakers at
AC output, Bypass
Input and AC Output.
(Shutdown is completed and UPS is isolated.)
* This operation is different from the displayed instruction on the screen.
Be sure to perform the procedure specified here.
DC INPUT
DC-V
0[V]
BATT-V 0[V]
BATT- I 0[A]
BYPASS
PRESS ‘RUN’ SWITCH
BATTERIES
AC
SWITCH
UPS
BYPASS
DISCHARGE
FLOAT CHARGE
EQUAL CHARGE
AC INPUT
~
CONVERTER
~
INVERTER
AC OUTPUT
BYPASS INPUT