Toshiba G8000 Series Power Supply User Manual


 
11
5. Installation Precautions
1) Install the unit in a well-ventilated location; allow at least 10 cm (4 inches) on all sides for air ventilation and
for maintenance.
2) Install the unit in a stable, level and upright position that is free of excessive vibration.
3) Install the unit where the ambient temperature is within the specified range.
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not install the UPS in areas that allow exposure to direct sunlight.
6) Do not install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or
flammable gases.
7) Do not install the UPS in areas near sources of electrical noise. Ensuring a proper earth ground will reduce
the effects of electrical noise and will reduce the potential for electrical shock.
8) Do not install the UPS in areas that would allow fluids or any foreign object to get inside the UPS.
9) The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are
installed inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that
are operating near by. If such interference is experienced, the UPS should be installed farther away from the
affected equipment and/or powered from a different source than that of the affected equipment.
10) The user should provide output over-current protection for hardwired UPS systems.
11) After ensuring that all power sources are turned off and isolated in accordance with established
lockout/tagout procedures, connect the power source wiring of the correct voltage to the input terminals of
the UPS.
12) Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and Article
310 – Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table
310.16.
Conductor Routing and Grounding
1) Use separate metal conduits for routing the input power, output power, and control circuits.
2) Follow the wire size and tightening torque specifications.
3) Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.
4) A separate ground cable should be run inside the conduit with the input power, output power, and control
circuits.
THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.
CAUTION
WARNING