Toshiba G8000 Series Power Supply User Manual


 
27
Table 2 Recommended Cable Size and Tightening Torque for 225kVA UPS.
The tightening torque must be greater than 90 percent of the recommended torque.
Cable Size and Tightening Torque for 225kVA UPS
(Only copper wires allowed)
Block Number Cable Size Tightening Torque
1 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
2 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
3 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
4 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
5 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
6 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
7 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
8 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
9 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
10 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
11 Two 2/0 or larger 5.8 kG-m (500 in-lbs)
12 Two 4/0 or larger 5.8 kG-m (500 in-lbs)
13 Two 4/0 or larger 5.8 kG-m (500 in-lbs)
NOTE: Maximum cable size is 350MCM.
*Two battery strings (consult factory if using one battery string).
Three cable knockout plates are provided at bottom of the 150/225kVA UPS. Holes are
recommended in Figure 6. The installing electrical contractor must punch the 5 holes.
3 solid rectangles show the cable knockout plates’ outline. The dashed rectangle
shows the UPS opening under the plates.
Figure 6 - Cable knockout plates at the bottom (150 and 225kVA).
0.4”
0.8”
4” Dia.
2” Dia.
AC Input Bypass
AC Output
Battery
Control
Wires
Plate #1
Plate #2
Plate #3