14.3.5 Changing Between Float Charge and Equalize Charge
This section shows the procedure to change the recharge mode between float charge and equalize
charge.
(1) Table 17 shows the procedure to change from float charge to equalize charge.
Table 17 - Change From Float Charge to Equalize Charge.
Step Procedure LCD/LED Status
1 Make sure that the
FLOAT CHARGE LED
is On.
2 Press FLOAT/EQUAL
button for 0.5 sec.
Change completed.
EQUAL CHARGE LED is On; FLOAT CHARGE LED is Off.
* In equalize charge mode, the battery is charged for a programmed period at a specified
voltage (depending on the battery spec) rather than the float charge, in order to prevent
voltage deviations among battery cells. This should be done once every six months if
possible.
The G8000 UPS has an automatic function to perform the equalize recharge after battery
backup operation.