59
16. UPS Specifications
16.1 General Specification
Terms Specification Remarks
Conforming Standard UL1778-2001 UL, cUL, IEC
Ambient Temperature 0°~40° C ( 32°~104° F)
Relative Humidity 30% ~ 90% Non-condensing
Altitude < 1,000m ( < 3,280ft )
Insulation Resistance 3M With 500V-Megger
Insulation withstanding AC 2kV – 1min. Main Circuit
voltage AC 1.5kV – 1min. External Interface
AC 500V – 1min. Electronic Circuit
Audible Noise 68dB(150/225kVA), 72dB(300kVA) 1m (39”) away from front
16.2 Mechanical Specification
Rated Capacity 150kVA 225kVA 300kVA
Cabinet Protection Conformity IEC298 IP20
(
*
)
Exterior Paint 2.8Y7.7/0.3
Panel Thickness Front 1.6mm (1/16”)
~ Back / Side / Top 1.2mm (3/64”)
~ Bottom 3.2mm ( 1/8”)
Input / Output cabling entrance Bottom Top
Ground / Control wiring entrance Bottom Top
Clearance in Front 1,100mm (43” 7/16)
~ in Back and Side 0mm (0”)
~ on Top 400mm (15” 3/4)
Outline Dimension (Width) 1,400mm (55” 1/8) 1950mm (76” 3/4)
(Depth) 800mm (31” 1/2) 900mm (35” 7/16)
(Height) 2,000mm (78” 3/4) 2,000mm (78” 3/4)
Weight 1,200kg (2,640lbs) 1,500kg (3,300lbs) 2,000kg (4,400lbs)
Floor loading per footprint 1,071 kg/m
2
1,339 kg/m
2
1,139 kg/m
2
( 219 lbs/ft
2
) ( 274 lbs/ft
2
) ( 233 lbs/ft
2
)
Heat Rejection 9,550 kcal/h 14,370 kcal/h 19,190 kcal/h
( 37,914 BTU/h) ( 57,049 BTU/h) ( 76,184 BTU/h)
(*) IP20 refers to foreign objects entrance and prevents objects of 12mm-diameter(15/32”) or larger.