Toshiba G8000 Series Power Supply User Manual


 
33
12.2.2 Operating Buttons
Table 7 shows the functions of the operating buttons on the graphic panel.
NOTES
Keep an operating button pressed for 0.5 seconds at least, when changing
UPS modes.
Keep the reset button pressed for 5 seconds to reset the UPS.
The UPS may not respond if this duration is too short.
Table 7 Button functions.
No. Name Function Remarks
RUN To start up the UPS.
The UPS starts up when this button is
pressed.
(Key-Switch in OPERATION mode)
STOP To stop the UPS.
The UPS stops when this button is
pressed.
(Key-Switch in OPERATION mode)
UPS
To transfer to normal operation
from bypass operation
The UPS transfers to normal operation,
if this button is pressed while bypass
operation.
(Key-Switch in OPERATION mode)
BYPASS
To transfer to bypass operation
from normal operation
The UPS transfers to bypass operation,
if this button is pressed while normal
operation.
(Key-Switch in OPERATION mode)
FLOAT / EQUAL
To flip the recharge mode
between float charge and
equalize charge.
The UPS flips recharge voltage between
float charge and equalize charge.
Equalize charge voltage can be
programmed as protection charge, with
battery overheat contact on, if desired.
(Key-Switch in OPERATION mode)
SCROLL UP
SCROLL DOWN
To scroll the LCD screens.
RESET
To reset the UPS faults and
warnings shown on the LCD.
See the section titled "LCD Scroll with
faults or warnings" and section "LCD
Scroll" for details.