Toshiba G8000 Series Power Supply User Manual


 
29
Table 4 - Recommended Lugs.
Recommendation
At Terminal Bus #
Vendor Catalog #
1
2
3
ILSCO
TA-600
AU-600
4
5
ILSCO
TA-600
T3A2-600N
6
7
8
TA-600
AU-600
9 TA-600, T3A2-600N
10
11
12
ILSCO
TA-600
AU-600
Four cable knockout plates are provided at the top of the 300kVA UPS. Holes are
recommended in Figure 7. The installing electrical contractor must punch the six holes.
Four solid rectangles show the cable knockout plates’ outline. The 3 dashed
rectangles show the UPS opening under the plates.
Figure 7 - Cable knockout plates at the top (300kVA).
0.8”
0.4”
4” Dia.
0.6”
1.5”
2“ Dia.
0.6”
1.5”
2“ Dia.
Plate #2
Plate #3
Plate #1
Plate #4
Ground
Wire
AC
Input
Battery Bypass
AC
Output
Control
Wires