56
15.2.4 LCD Scroll with faults or warnings.
When the UPS has stopped due to a fault, be sure to remove the
memory card before resetting the LCD Fault Error screen on the
panel.
Resetting (restarting) the UPS without removing the memory card will delete
the data needed to determine the cause of the fault.
When removing the memory card, do NOT touch the other sections
of the UPS.
Option:
NOTES
Touching the other sections of the UPS may result in electric shock.
This section describes how to scroll through the LCD screens when a fault has occurred (when Fault
Data screens exist).
Figure 20 shows the locations of the buttons to scroll the LCD screens. See Table 27 and Figure 21 for
detail of the scroll buttons and how they are used for screen scrolling.
Note that pressing the "RESET" button will delete the waveform data stored on the memory card as
well as the Fault and Warning Data Screens. Be sure to remove the memory card before pressing the
"RESET" button.