Toshiba G8000 Series Power Supply User Manual


 
39
5 Measurement screen #3
Output current (peak)
Shows the output current peak (%) for each
phase.
Peak value of output current
RMS value for rated current × 1.41
× 100 [%]
6 Measurement screen #4
AC input
Shows the voltage and frequency of the AC input.
7 Measurement screen #5
Bypass input
Shows the voltage and frequency of the Bypass
input.
8 Measurement screen #6
Battery
Shows the rated battery backup time with rated
load and cumulative discharged time.
9 Measurement screen #7
DC circuit
Shows the DC bus voltage, battery voltage and
battery current.
Negative battery current stands for recharge
current and positive stands for discharge.
10 Measurement screen #8
Counter values
Shows the cumulative UPS operation time, the
cumulative battery backup time and the number of
battery backup operations.
11
Measurement screen #9
Clock
Shows the present time.
( 24-hour clock )
O/P CURRENT (PEAK)
U 50[%]
V 50[%]
W
50[%]
AC INPUT
AC I/P-V 480[V]
FREQ. 60.0[Hz]
BYPASS INPUT
BYP I/P-V 480[V]
FREQ. 60.0[Hz]
DC INPUT
DC-V 632[V]
BATT-V 400[V]
BATT- I 0[A]
MODE COUNT
UPS 35[H]
BATTERY 56[MIN]
32[TIM]
BATTERY
BACK-UP RATING
10[MIN]
DISCHARGING 15[MIN]
CLOCK
TIME 03-24-02 12:58