Tripp Lite SU120KX2 Power Supply User Manual


 
1
5
9
3
7
11
2
6
10
4
8
12
13
14
1
2
43
10-5-4 Charger Setup
Use “ ” or ” ” to select “CHARGER”, then press ” ” to confirm.
From the “CHARGER CURRENT” screen, use the scroll buttons
( , ) to select the desired setting and press the enter button
( ) to confirm the setting.
Each internal power module has a 5-amp maximum charger.
Charger current can be set from a minimum 2 amps total to a
maximum of 5 amps (or max current determined by a charging
rate C/4 in a per-power-module base, whichever is smaller)
multiplied by the number of modules. The SU120KX2 with six
internal power modules has a charger current range of 2-30
amps. Set the charger current value based on the size of the
battery system. See Section 10-5-3 for more information about
determining the size of the battery system.
Warning: Setting the charger current too high may damage
batteries and reduce their operational lifespan. Consult the
factory or your authorized Tripp Lite service technician for
guidance before changing the default setting.
Press “ ” or ” ” to change the charging current, then press
” to confirm.
Press “ESC” to return to the “UPS SETUP” menu.
1
2
10 – Display and Configuration (continued)
12-212-93-3141.indb 43 12/28/2012 11:18:08 AM