12 – Specifications
12-1 UPS System Technical Specifications
12-2 UPS System Floor Loading Table
Capacity 120KVA/96KW
Input
Rating Voltage V
220/380, 230/400, 240/415
(3Φ 4W+PE)
Voltage Regulation % <70% Full Load: -48/+20 (at 230/400V); Full load: -25/+20 (230/400V)
Input Current Harmonic Distortion (Full
Load)
% < 4
PFC (Full Load) > 0.99
Frequency Hz 50 / 60
Frequency Tolerance Hz 45 ~ 65
Output
Output Voltage V 220/380, 230/400, 240/415 (3Φ 4W+Earth)
Output Frequency Hz 50 / 60
Total Harmonic (Linear Load) % 3
Voltage Regulation Static % ±1
Dynamic % 7 (Max Deviation for 10% ~ 90% Linear Load)
Frequency Regulation Interior Oscillator Hz ±0.05
Synchronized % ±5
Overload 125%: 10 minutes ; 150%: 1minute
Audible Warning
Battery Backup Intermittent
UPS Abnormal Continuous
Display
LED UPS status: Normal, Bypass, Backup and Fault
LCD
Input/Output, Bypass, Inverter, Frequency, Loading and Battery voltage, current,
UPS abnormal message and intelligent self diagnostics
Remote
Monitor
Monitor up to 31 PCs, Graphically display records and historical data and
Fault records retrieved
Control Remote control the Inverter and alarm, setup password and auto-dial warning
Interface
Standard RS232, Dry Contact Output/Input
Optional
SNMP card, Modbus card, Relay I/O control card, Environmental sensor box,
SNMP+5 Ports Hub
Others
Parallel Configuration Up to 4 UPS systems of the same capacity for redundancy capacity
EPO Standard (Local and Remote)
SRAM Event Log Yes (500 records)
Parameter Configuration Yes
Hot Standby Installation Feasible
Battery Temperature Compensation Optional
Battery Cold Start Standard
Overall
Efficiency (at full load)
Normal % 94
ECO % 97
Transfer Time ms 0
Operating Temperature °C 040
Humidity (Non-Condensing) % 90
Noise (@ 1 m) dBA 70
Dimension Width mm 520
Depth mm 975
Height mm 1695
Weight Kg 379
Model SU120KX
Weight 379 kg
Floor Loading 748 kg/m²