10-5-5 Parallel Setup
Use “ ” or ” ” to select “PARALLEL”, then press ” ” to confirm.
Use “ ” or ” ” to select the desired item, then press ” ” to
confirm.
Parallel Group
The parallel group setting tells the UPS that it is operating in
parallel. System configuration Group 1 is the default setting. See
Section 6 – Wiring for wiring considerations. Note: Possible
settings are 1 or 2.
Parallel ID
Identifies the UPS number (1-8) within the group. When
paralleling UPS systems, each must have a unique Parallel ID. Up
to four (4) SU120KX2 UPS systems may be paralleled.
Press “ESC” to return to the “UPS SETUP” menu.