Agilent Technologies E1301B Computer Hardware User Manual


 
1
Start-up Error
Messages
Start-up errors are most often generated just after the mainframe is powered-up
or re-booted (DIAG:BOOT command). If you have an Agilent E1301B, or an
Agilent E1300B with a terminal connected to the Display Terminal Interface
(built-in RS-232 only), you can read these errors on the front panel or terminal.
If you have an Agilent E1300B and no terminal, then you must access this error
information by sending the VXI:CONF:DLIS? command over GPIB. We
recommend that users of either model include a routine at the beginning if their
application program which checks for start-up errors before the program trys to
access individual instruments. See your Installation and Getting Started Guide
for an example program.
Start-Up Error Messages and Warnings
Code Message Cause
1 Failed Device VXI device failed its self test.
2 Unable to combine device Device type can not be combined into an
instrument such as a scanning voltmeter or a
switchbox.
3 Config warning, Device
driver not found
ID of device does not match list of drivers
available. Warning only.
5 Config error 5, A24 memory
overflow
More A24 memory installed in the mainframe
than can be configured into the available A24
memory space.
8 Config error 8, Inaccessible
A24 memory
An A24 memory device overlaps a memory
space reserved by the mainframe’s operating
system.
10 Config error 10, Insufficient
system memory
Too many instruments installed for the amount
of RAM installed in the mainframe. Cannot
configure instruments. Only the system
instrument is started.
11 Config error 11, Invalid
instrument address
A device’s logical address is not a multiple of 8
and the device is not part of a combined
instrument.
13 Config error 13, Logical
address or IACK switch set
wrong
Duplicate logical addresses set or interrupt
bypass switches set improperly. Only the system
instrument is started.
29 Config warning, Sysfail
detected
A device was asserting SYSFAIL on the
backplane during startup.
30 Config error 30, Pseudo
instrument logical address
unavailable
A physical device has the same logical address as
IBASIC (240)
31 Config error 32, File system
start up failed
Insufficient system resources to allow the
IBASIC file system to start.
45 Config warning, Non-volatile
RAM contents lost
NVRAM was corrupted or a cold boot was
executed.
48 Config warning, Driver RAM
contents lost
Driver RAM was corrupted or a cold boot was
executed.
Table B-3. Start-up Error Messages and Warnings
Error Messages B-5