APC AP9631 Network Card User Manual


 
97UPS Network Management Card 2 User’s Guide
SNMP Issues
Synchronization Problems
Problem Solution
Unable to perform a
GET
• Verify the read (GET) community name (SNMPv1) or the user profile configuration
(SNMPv3).
• Use the command line interface or Web interface to ensure that the NMS has access.
See “SNMP” on page 67.
Unable to perform a
SET
• Verify the read/write (SET) community name (SNMPv1) or the user profile
configuration (SNMPv3).
• Use the command line interface or Web interface to ensure that the NMS has write
(SET) access (SNMPv1) or is granted access to the target IP address through the
access control list (SNMPv3). See “SNMP” on page 67.
Unable to receive
traps at the NMS
• Make sure the trap type (SNMPv1 or SNMPv3) is correctly configured for the NMS
as a trap receiver.
• For SNMP v1, query the mconfigTrapReceiverTable APC MIB OID to verify that
the NMS IP address is listed correctly and that the community name defined for the
NMS matches the community name in the table. If either is not correct, use SETs to
the mconfigTrapReceiverTable OIDs, or use the command line interface or Web
interface to correct the trap receiver definition.
• For SNMPv3, check the user profile configuration for the NMS, and run a trap test.
See “SNMP” on page 67, “Trap Receivers” on page 74, and “SNMP Trap Test” on
page 75.
Traps received at an
NMS are not
identified
See your NMS documentation to verify that the traps are properly integrated in the
alarm/trap database.
Problem Solution
A Synchronized Control Group
member does not participate in a
synchronized action.
Make sure the group member’s status is set to Enabled. Also check the
group member’s battery capacity, if the synchronized action required
UPSs to turn on.
An attempt to add a member to a
Synchronized Control Group fails.
The values for Multicast IP Address, Synchronized Control Group
Number, and firmware version must match those of other members of
the group.