APC AP9631 Network Card User Manual


 
35UPS Network Management Card 2 User’s Guide
Configuration Pages
The power option
This option is available for all UPS models.
The available settings differ based on the UPS model. For detailed information about fields
and values available through the power option and specific to your UPS model, see the online
help.
You can configure the following types of model-specific items:
Put UPS To Sleep
(Web interface)
ups -c Sleep
(command line
interface)
Puts the UPS into sleep mode by turning off its output power for a defined period of
time:
• The UPS turns off output power after waiting the time configured as Shutdown
Delay. See “The shutdown option” on page 36.
• When input power returns, the UPS turns on output power after two configured
periods of time: Sleep Time and Return Delay. See “The shutdown option” on
page 36.
• For a synchronized control group action, the Management Card of the initiating
UPS waits up to the number of seconds configured as Power Synchronized Delay
for enabled group members to regain input power before it starts the Return Delay.
If all group members already regained input power, the Power Synchronized
Delay is omitted. If all group members regain input power during the delay, the rest
of the delay is cancelled. See “Configure a Synchronized Control Group member”
on page 43.
ups -c
GraceSleep
(command line
interface)
Puts the UPS into sleep mode (turns off power for a defined period of time):
• The UPS turns off output power after waiting the Maximum Required Delay to
allow time for PowerChute Network Shutdown to shut down its server safely, and
its Shutdown Delay. See “Maximum Required Delay” on page 36 and “The
shutdown option” on page 36.
• When input power returns, the UPS turns on output power after two configured
periods of time: its Sleep Time and Return Delay Time. See “The shutdown
option” on page 36.
• For a synchronized control group action, the Management Card of the UPS
initiating the action waits up to the number of seconds configured as its Power
Synchronized Delay for enabled group members to regain input power before it
starts the Return Delay. If all group members have already regained input power,
the Power Synchronized Delay is omitted. If all group members regain input
power during the delay, the remainder of the delay is cancelled. See “Configure a
Synchronized Control Group member” on page 43.
Put UPS In Bypass
and Take UPS Off
Bypass (Web
interface)
ups -b Enter
ups -b Exit
(command line
interface)
Controls the use of bypass mode, which allows maintenance to be performed at a
Symmetra UPS and some Smart-UPS models without turning off power at the UPS.
Action Definition