Bay Technical Associates DS62 Network Card User Manual


 
DS62-Network, DS62-MD4 Network/Modem Host Module
37
Option 1 and 3 sets the temperature levels to the tenth of a degree. Option 2 and 4 enable the SNMP
traps to be sent if the corresponding threshold had been exceeded.
Select 2), ‘All Sensors’ option allows the administrator to set parameters for the different probe types.
This feature is useful for standardization and the probe type is not known due to its final location is not
known. The DS displays:
NOTE: The type ‘Contact’ signifies the unit does not recognize or detect a probe, but still be
able to send SNMP Traps.
Select the specific option to set the High and Low alarm ranges and their corresponding SNMP traps.
Outlet Groups
This is a future option not currently used. This option sets up the outlets into groups.
Sel Type Name Hi/En Lo/En St/En
1 Contact External Sensor1 N/A N/A En
2 Temperature External Sensor2 999/En 320/En N/A
For configuration of all sensors of selected type in system with a
single user-supplied value.
1...Contact
2...Temperature
3...Humidity
4...Air Flow
Enter Request :1
DS/RPS External Environmental Sensor Configuration Menu
Sensor Number: All Name: all DSs/RPSs Type: Temperature/Humidity/Air Flow
1...High Threshold (tenths of meas. unit): NP
2...High Threshold Trap Enable: NP
3...Low Threshold (tenths of meas. unit): NP
4...Low Threshold Trap Enable: NP
Enter Request :
Enter threshold value in tenths of unit measurement (degrees,%%,etc.):
Outlet Group Configuration:
List Outlet Groups...............1
Add Group........................2
Delete Group.....................3
Rename Group.....................4
Modify Outlets in a Group........5
Delete All Outlet Groups.........6
Enter Request :1