DCS 500 Power Supply User Manual


 
Chapter 3 - Handling of Control Panel CDP 31x
DCS 500B / DCP 500B Operating Instructions IV A 3 - 9
3.8 Fault History Display
Up to 100 faults are stored time related and displayed together with
the time they appeared after electronics supply switched on.
Step Function Press key Display after key is
pressed
1.
To enter the Actual Signal
Display Mode
ACT
0 L 0.0 rpm 00
SPC:OUT 0.0 %
CONV CUR 0 A
U ARM AC 0 V
_
2. To enter the Fault History Dis-
play.
These keys also scroll the
screen from Actual Signal Dis-
play to Fault Display, to Fault
History Display back to Actual
Signal Display.
0 L 0.0 rpm 00
1 LAST FAULT
+Type code changed
xxxx:xx:xx.xx
3.
To select newer (UP) or older
fault (DOWN).
To clear a fault from the Fault
History Buffer
The previous fault is displayed.
Drive condition identical to 3.6
and 3.7
RESET
0 L 0.0 rpm 00
2 LAST FAULT
Armature overvoltage
xxxx:xx:xx.xx
0 L 0.0 rpm 00
1 LAST FAULT
Reset
xxxx:xx:xx.xx
4.
To return to the Actual Signal
Display Mode.
0 L 0.0 rpm 00
SPC:OUT 0.0 %
CONV CUR 0 A
U ARM AC 0 V
_
3ADW000055R0401_DCS500B_Operating Instruction_e_d