46
Press
ENT
to enter Open Time setting. In the menu shown below, press numeric key
1~8 to enter the desired door number in the Door field. (The max number depends
on the actual door modules installed in the controller) Enter the desired door open
time in the OpenTime field: enter minutes as a 3-digit number 0~999, and enter
seconds as a 2-digit number 0~59. Press
ENT
to confirm. Press to exit without
effecting any change.
Set Door Hold Open Time
Door sensor monitors the open/close status of a door. If normal open is not set by
the system (door is normally considered closed), then door should close after opening
for a while. It is considered abnormal if controller does not receive the door close
signal from door sensor a reasonable amount of time after the door is opened. This
time period is call door hold open time or door over time. According to this setting,
EverAccess controller will determine whether to generate an alarm or not after the
door sensor timeouts. The default value of door hold open time is 5 seconds. The
maximal door hold open time supported by the controller is 999 minutes and 59
seconds.
At the following submenu:
Press
ENT
to enter Door Hold Open Time setting. In the menu shown below, press
numeric key 1~8 to enter the desired door number in the Door field. (The max
number depends on the actual door modules installed in the controller) Enter the
desired door hold open time in the OpenTime field: enter minutes as a 3-digit
number 0~999, and enter seconds as a 2-digit number 0~59. Press
ENT
to confirm.
Press to exit without effecting any change.
Set Door Behavior at Fire Alarm
The controller allows the user to choose one of two behaviors to occur when a fire
alarm is triggered: fail-safe or fail-secure. Door fail-safe at fire alarm means the door
will be kept unlocked when there is a fire alarm input. Door fail-secure at fire alarm
means the door will be locked when the fire alarm comes in. At the following
submenu:
Door:[_]
OpenTime
:
___M__S
Over Time
Setting
Door:[_]
OverTime
:
___M__S
Door Control
at Fire Alarm
CLR
CLR