EverFocus EFC--02-1-A Network Card User Manual


 
47
Press
ENT
to enter Door Control at Fire Alarm setting. In the menu shown below,
press numeric key 1~8 to toggle the door control between fail-safe and fail-secure.
(The numbers correspond to the number of door modules installed in the controller)
“Y” indicates fail-safe; “N” indicates fail-secure. Press
ENT
to confirm. Press to
exit without effecting any change.
The default setting for door control at fire alarm is all the doors are fail-safe, i.e. all the
doors will be unlocked during a fire alarm.
Alarm Setting
EverAccess Flex controller is equipped with powerful alarm functions. With alarm
modules and door modules fully installed, the controller can accommodate up to 10
alarm inputs and 18 alarm outputs. At the meantime, EverAccess Flex controller also
provide very flexible configuration. Any event can be arbitrarily allocated to single or
multiple alarm outputs. Alarm components, configuration basics, and menu settings
are introduced below.
Components for Alarm
EverAccess Flex controller consists of two basic components: one main module and
one door module. User can install three more door modules and one alarm module.
These three types of module are all equipped with alarm function. The main module
has 2 alarm inputs, corresponding to fire alarm and Alarm In 0 . It has 2 alarm
outputs as well, called Main Alarm Output and Auxiliary Alarm Output respectively.
Each door module has 2 alarm outputs, which usually react to alarm events on the
corresponding door. However, it can be set to react to other alarm events as well.
Alarm outputs on the door module can connect up to 5A external alarm devices.
Alarm module has 8 alarm inputs and 8 alarm outputs. 8 alarm inputs can connect to
external alarm input devices, such as PIR motion sensor, glass sensor and etc. 8 alarm
outputs can connect up to 2A external alarm devices.
The above mentioned are physical devices providing alarm function. User can freely
define the allocation of any input to any output. The following section outlines basic
concepts for events, alarm and configuration.
Alarm Configuration Basics
EverAccess Flex controller keeps tracking all events in the access control system,
either legal or illegal, either normal or abnormal, for example, the granted access, the
denied access and so on.
12345678
YYYYYYYY
CLR