Enclosure events
www.gateway.com
Encl.
yy
Temp.
zz
<
aa
>C
Warning WWN:
xx xx xx xx
xx xx xx xx
The controller has detected
that the indicated
temperature sensor has
reached a warning limit.
Temperature
sensors are
reporting
enclosure
temperatures have
reached the
threshold of 70°C.
Automatic system
shutdown will
begin.
Make sure that
both cooling fans
are operating
normally. (Replace
if needed.)
If the fans are set
to automatic
speed control,
place the jumper
on the Cooling fan
module circuit
board to force the
fans to high speed.
If the environment
ambient
temperature is
high, reduce the
ambient
temperature.
Make sure that the
airflow is not
blocked or
restricted on the
enclosure.
SES Event Messages Description Cause Action