Chapter 9: Event Logs
www.gateway.com
Encl.
yy
Temp.
zz
<
aa
>C
Critical WWN:
xx xx xx xx
xx xx xx xx
The controller has detected
that the indicated
temperature sensor has
reached a critical limit.
Temperature
sensors are
reporting
enclosure
temperatures have
reached the
threshold of 50°C.
If the fans are set
to automatic
speed control,
place the jumper
on the cooling fan
module circuit
board to force the
fans to high speed.
If the environment
ambient
temperature is
high, reduce the
ambient
temperature.
Make sure that the
airflow is not
blocked or
restricted on the
enclosure.
Encl.
xx
Alarm
zz
is OFF
WWN:
yy yy yy yy yy yy
All conditions are normal or
the alarm is off.
No condition being
reported.
Alarm silenced.
No action
necessary.
User pressed the
Alarm Silence
button on the front
panel.
Encl.
xx
Alarm
zz
is ON
WWN:
yy yy yy yy yy yy
Alarm is on. A condition
caused the alarm
to sound.
Press the Alarm
Silence button on
the front panel and
isolate the cause
of the alarm.
SES Event Messages Description Cause Action