GE EPM 7700 Network Card User Manual


 
92 PMCS Interface Toolkit
565 Feeder Management Relay
The large faceplate representation of the 565 provides the following animated
functions:
Feature Function
Display Window Opens the tabular data window specified during wizard configuration and sets the view to Monitoring page.
SET POINTS
Button
Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.
RESET Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.
CLEAR Button Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.
NEXT CHOICE Opens the tabular data window specified during wizard configuration and sets the view to the Setup page.
0 to 9 Buttons Open the tabular data window specified during wizard configuration and set the view to the Setup page.
HELP Button Displays a Windows help screen for PMCS.
ACTUAL
VALUES Button
Brings the meter to an initial setting point and displays ACTUAL VALUES HAS NINE PAGES OF DATA.
REFRESH Button Updates the display to the current meter reading.
STORE Button Resets the meter at six special points in the display of values. Press STORE to toggle the response on the
bottom line.
PAGE UP Button Rotates among nine pages of parameter data. Press the key to display ACTUAL VALUES on the top line, a
description on the bottom, and reset to the first parameter value. The nine pages are listed in the table below.
LINE Buttons Rotate among parameters within a page. Certain configurations or meter values may prevent display of all
parameters within a page. The parameters in each page are listed in the table below.
Panel Display
Lights
Display animation that shows the status of the 565 relay. The dark red square to the left of the label appears
bright red to indicate an active state. The TRIP bar shows the current trip condition. Auxiliary relays 1, 2, and
3 show user-selected function status. The BREAKER CLOSED and BREAKER OPEN bars show the status
of the monitored feeder breaker. The SERVICE bar is not animated.
Table 11. 565 Faceplate animated functions.
The following table lists the pages that can be accessed with the PAGE UP button,
with the parameters available in each page that can be accessed with the LINE buttons.